Ford Rouge Power Plant Explosion & Investigation

Posting by Discussion Group Member Roland O'Brien-Bills, Accident Investigations.

What other safety mechanisms - besides blanking and shutting off the valves - were in effect or should have been in effect?

There was a Gentleman in earlier correspondence that suggested blanking is unwise and I agree, for I have inspected boilers and burner fronts for years. Double shut off valves is the proper way to secure a gas line with venting. This bit map schematic -below- is an approximation of what I would expect as a minimum arrangement for the gas piping for igniters. This schematic suggests there are safe guards of at least two levels. They are Block valves and Vents.  If either of the block valves leaked by, then gas pressure could build-up and pour into the furnace only if the vents are plugged. If the work order required the workers to replace the IHSSV (Igniter header safety shut-off valve) then the gas line header in the steam/power plant should have been shut down. This line also has a safety vent.

Was the vent plugged, which runs to the roof or safe point of discharge outside of the building, or the burner management system instrumentation wiring had been modified inadvertently? The burner management interlock system is made to prevent this mishaps like this one.


- Schematic of Minimum Safe  Valve 'Shut-Off' Design-

gasignitors.gif (83126 bytes)

What safety, performance, design and/or inspection standards apply to gas line valves (which are not regulated by boiler regulations)?

I would like to make these generalized comments: The NFPA and insurance companies writing property and casualty policies set the pace for the burner management system. Furthermore, Jurisdictions use the NFPA or a mirror image of it. As a rule, most Fire Insurance inspectors are not boiler people; consequently, the fire inspector may over look the inspection and testing of the burner management system. The boiler inspector like the National Board of Boiler and Pressure Vessel Inspectors are interested only in the pressure retaining components and not the burner front. The Jurisdiction, where the insurance boiler inspector has his commission, is interested in the burner management and pressure retaining components of the boiler (true most jurisdictions). The insurance fire inspector is interested in the furnace explosion aspects that encompasses the burner management system and burner front.

Can anyone identify any companies who make gas valves such as may have been used in the Rouge power plant?

I would like to say this about safety block valves (more applicable to question 2): They are FM, UL, etc... tested or they met those agencies' criteria. This decreases the probability off the shelve faulty block valves because of the serious nature in which they are used. They are difficult to tamper with, but not impossible. They may leak like any valve after a number of cycles.

Roland O'Brien-Bills
Roland_O'Brien-Bills@Accidents-Inspections.com

Join Moderated Discussion List!

Please Read Disclaimer Before Proceeding!

Receive regular updates and new information
surrounding the explosion and ongoing investigation.

Enter your email address below,
then click the 'Join List' button:

Subscribe Unsubscribe

 


Please read the Disclaimer.

Webmaster: C. Enrico Schaefer, Esquire
email: rougeplant@excite.com
instant message: click here

616-256-7399



The Ford river rouge plant boiler valve explosion explode blast fire boiler at the power plant. The steam generator asbestos coal furnace powerhouse dust pressure cause investigation. A defective investigator investigate Michigan MI, Detroit news links. Victims were burn burned burns at the ford river rouge plant explosion boiler power plant facility complex.

The Ford river rouge plant boiler valve explosion explode blast fire boiler power plant. The steam generator asbestos coal furnace powerhouse dust pressure cause investigation. A defect defective investigator investigate Michigan MI, Detroit news links. Victims were burn burned burns at the ford river rouge plant explosion boiler power plant facility complex.

The Ford river rouge plant boiler valve explosion explode blast fire boiler power plant. The steam generator asbestos coal furnace powerhouse dust pressure cause investigation. A defect defective investigator investigate Michigan MI, Detroit news links. Victims were burn burned burns at the ford river rouge plant explosion boiler power plant facility complex.

Information and Links Regarding Ford Rouge Power Plant Explosion.